Non-Compliance detail


  
Summary
 
Licence number: 837
Annual Return Start: 02 May 2010
Annual Return End: 01 May 2011
Date Received: 01 Jul 2011
 
Licence Condition numberType of non-complianceEPA actionsNo. of times occurred
O2.1 A loss of containment of high normal naphtha (HNN) occurred via the tanks water draw system. Shell side valve was found fully open & downstream valve not isolated. HNN recovered & reprocessed thru oil drainage system, 19 May 2010. Penalty Notice issued 1
L1 Pollution of waters due to flood event resulted in flooding at wastewater treatment plant, adjacent properties & oily discharge to Towra Point Nature Reserve & Botany Bay: 3 June 2010; 20 March; 27 April 2011. PRP to address non-compliance(s) issued 3
M2.1 The NOx 45F-100X analyser availability for the year has been 33%. Issues relating to its auto zeroing & air purging functions. Calibrated for max stack temp of 280 degrees which is regularly exceeded. Sample loop to be installed in Sept 2011. Appropriate Action taken by licensee 1
L9 65 calls received regarding odour in licensing period. Meteorological &/or operational conditions cause odours. All complaints investigated. Reducing potential sources of odour & timing of activities. S.58 notice issued to change/amend licence conditions(s) 1